Chongqing Zhongneng Oil Purifier Manufacture Co., Ltd.

Fully automatic insulating oil dielectric strength tester/ withstand/ oil anayzer

Fully automatic insulating oil dielectric strength tester/ withstand/ oil anayzer
Product Detailed

For many electric equipments used in power system and enterprises, inner insulation is mostly oil-insulated. Oil dielectric stre

Product Description

For many electric equipments used in power system and enterprises, inner insulation is mostly oil-insulated. Oil dielectric strength test is one of the essential routine tests. IIJ-II Oil Dielectric Test Set is the ideal testing device for oil dielectric strength. The test sets are fully automatic. 

Features :
1) Fully automatic, control by microcomputer, utilization of new I/O terminal.
2) Numbers of times of testing and idling time of stirring are set via digital setting.
3) Test results displayed and printed out automatically.
4) Strong capability of anti-interference.
5) High accuracy of testing and high capacity of anti-jamming.
6) Easy to operate, small size, light weight which operated in the open air very conveniently and convenient for maintenance
7) Can store 99 groups oil testing data which is convenient to reading and print. The testing data can keep 100 years under the condition of power off.

8) System time can go on running under power off.(the system time just for reference can not be the standard of timing)

 

Technology and parameter data

1. Power supply: AC220V 10%, 50 HZ

2. Voltage output: 60 KV, 80KV, 100KV

3. Capacity: 1.6KVA, 2.0KVA

4. Pressure increase rate : About 2 KVA/S

5. Pressure testing speed: 3%

6. Break down sensitivity : <2KV

7. Wave form distortion :≤3%

8. Time of break down: ≤10ms

9.  Operational environment: Temperature:0°C-40°C, Humidity: the most relative humidity85%

10. Storage environment : Temperature:-20°C-40°C, Humidity: the most relative humidity75%.

11. Operational height: <150m (can be specially designed if the height is over 1500m)

12. Test cell: Glass, volume 300 to 500 ml, with protective cover and stirrer.

13. Electrodes: Stainless steel spherical 36 mm diameter/hemispherical 25 mm radius, 2.5 mm gap as

per IEC-156.

14. Nitial stand time of oil sample: 180 seconds

Intermediate stand time of oil sample: 60 seconds

String time of oil sample:  60 seconds

Number of consecutive test: 6

15. Weight for High voltage and control: Total about 50kg

 



Copyright Notice @ 2008-2022 B2BAGE Limited and/or its subsidiaries and licensors. All rights reserved.